TitleProduct

Gas Safety Shut Off Valve

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2021-08-10 06:34

  • Browse the number:

    269

Send an inquiries

Company Profile

Zhejiang Sanhao Intelligent Technology Co., Ltd

By certification [File Integrity]

Contact:zhejiangsanhao(Mr.)  

Email:

Telephone:

Phone:

Area:Beijing

Address:Beijing

Website:http://www.madagas.net/ http://zhejiangsanhao.ahedong.com/

Product Details

Gas safety shut off valve

MVDLE/5

Technical Description

The MVDLE/ 5 series safety solenoid valves are single-stage automatic shut-off valves that meet the requirements of EN 161 for gas burners and gas equipment.

- Pipe thread as per ISO 7/1

- MVDLE: Slow opening with adjustable fast stroke for start gas volume

- Flange connection as per DIN EN 1092-1


MVDLE/5

Gas safety shut off valve, normally when closed, slow opening, fast closing. Opening time adjust- ment with fast stroke range. Main volume adjustment.


Specifications

Nominal diameters

Pipe thread as per ISO 7/1, Rp

Flange

DN20

Rp3/4

Connection flange (PN 16) as per DIN EN 1092-1

Max. operating pressure

Up to 360 mbar (36 kPa) or up to 500 mbar (50 kPa) - refer to type overview

Solenoid valve

Valve as per EN 161, Class A, Group 2, single-stage mode

Closing time

< 1 s

Opening time

For MVDLE approx. 20 s at room temperature 20 °C and without fast stroke

Fast stroke

Adjustable

Main volume adjustment

Manually adjustable on MVDLE

Materials of gas-conveying parts

Housing: aluminium, steel, brass

Seals: NBR basis

Voltage/frequency

230 V AC (+10 % -15 %); 50-60 Hz - other voltages on request

Solenoids 60E, 61E in 24-28 VDC

External activation of solenoid coils required, see operating and mounting instructions

Rating / power consumption

Refer to type overview

Switch-on duration

100 %

Degree of protection

IP 54, IP 65 on request

Switching rate

MVDLE…/5: max. 100/h

Measuring/ignition gas connection

G 1/4 ISO 118, on both sides in inlet section, additionally G 3/4 on input side, form size DN 40 (flange) upwards

Dirt trap

Sieve installed, mesh width 1 mm

Ambient temperature

-15 ° C to +60 °C

Installation position

Solenoid from vertically upright to horizontally lying

Closed position signal contact

MVDLE/5: Type K01/1, DIN-tested, mountable on DN 10 - DN 150

Valve proving system

Type VDK 200 A S02, mountable via G 1/4 test connection, Type VPS 504, mountable with adapter up to DN 80


Type

pmax.

DN / Rp

Solenoid-No.

Pmax.

[VA]

I max.

~ (AC)

230 V

Opening time

Dimensions

[mm]

Weight

[kg]

øa

b

c

d

e

f

MVDLE207/5

360

Rp 3/4

200

30

0,15

ca. 20 s

75

100

165

85

190

190

2,55




Gas solenoid valve installation

1. First of all, we should check whether the working environment of gas solenoid valve products meets the work conditions, including temperature, pressure, medium attributes, etc.Check whether the components of the solenoid valve are missing structural stability. The general coil is in the same direction as the horizontal pipe except for special models.Please check the manual carefully before installation.


2. Check the cleanliness of the working environment and internal parts, so that no visible debris, if there are large debris in the work into the solenoid valve will cause some damage to the solenoid valve.


3. In the key parts of explosion-proof gas solenoid valve device pressure gauge.And pay attention to the monitoring of the solenoid valve pipeline pressure, once exceed the standard to take the corresponding corresponding measures in time, so as to avoid unnecessary losses caused by accidents.


4. When installing the gas solenoid valve, we should see the arrow mark on the valve body, which indicates the direction of medium transmission, of course, it can be ignored in special circumstances.


5. Gas solenoid valve generally has two types of normally open and normally closed, can not be used interchangeably, otherwise it is easy to cause damage to the solenoid valve, reduce the service life of the solenoid valve.


6. Gas solenoid valve products are divided into normally closed and normally open type, do not mix the wrong use, because the wrong mixed use will make the solenoid valve product damage.It is best to have a bypass to troubleshoot in case of an emergency.

Different media should be suitable for different materials of gas solenoid valve, rational use can make it play the maximum benefit, in the choice of gas solenoid valve products to timely reflect the conditions such as working conditions, so as to select the right and reasonable model.


MVDLE 207/5

Setting the main flow


MVDLE 207/5

Rapid stroke adjustment V start

Factory setting MVDLE 207/5: Rapid stroke not adjusted

1. Unscrew the adjustment cap D from the hydraulic brake.

2. Invert the adjustment cap and use as a tool.

3. Turn anti-clockwise = increase rapid stroke (+).



Replacing hydraulic brake unit

1. Switch offff fi ring system.

2. Remove locking varnish from countersunk screw A.

3. Unscrew countersunk screw A.

4. Unscrew socket head screw B.

5. Raise hydraulic brake C.

6. Exchange hydraulic brake C.

7. Screw in countersunk and socket head screw. Only tighten socket head screw so that hydraulic brake C can just be turned.

8. Coat countersunk screw A with locking varnish.

9. Leakage test: Pressure tap at sealing plug 2:

MVD 2 …pmax.= 200/360 mbar

MVD 5 …pmax. = 500 mbar

10. Perform functional test.

11. Switch on fi ring system.


We reserve the right to make any changes in the interest of technical progress.

ITALY MADAGAS TECHNOLOGY LIMITED

Telefon +86-133 6276 8518

Telefax 0577-62869980

WeChat public address:renengegou

ch3h@ch3ch.com